大家都知道集(ji)中電(dian)源集(ji)中控制系統已經逐步取代傳統應急疏散成為一般公共建筑的消防安全常備系統。但是為了保證其能夠在真正的火災現場正常工作,那也是需要定期給它做維護的。
集中(zhong)電(dian)(dian)源(yuan)集中(zhong)控(kong)制系(xi)(xi)統(tong)(tong)將復雜的(de)電(dian)(dian)子電(dian)(dian)路放(fang)置(zhi)在專用(yong)房間,應急照明燈與普通(tong)燈一樣,一般(ban)電(dian)(dian)工(gong)可以進行維護;隨(sui)著現代技術(shu)的(de)發展,許多廠家生產(chan)的(de)集中(zhong)電(dian)(dian)源(yuan)集中(zhong)控(kong)制系(xi)(xi)統(tong)(tong)也具有自(zi)己的(de)自(zi)動檢(jian)測功(gong)能,可以通(tong)過(guo)自(zi)己的(de)計算機(ji)通(tong)信接口向上位機(ji)發送信號,并利用(yong)計算機(ji)對其(qi)進行監控(kong)和管(guan)理(li)。即使在系(xi)(xi)統(tong)(tong)中(zhong)沒(mei)有設置(zhi)計算機(ji)管(guan)理(li),它仍然使用(yong)監控(kong)系(xi)(xi)統(tong)(tong)本身。當電(dian)(dian)源(yuan)出現故障(zhang)或電(dian)(dian)源(yuan)即將耗(hao)盡(jin)時,會發出聲光報(bao)警,大(da)大(da)減少了系(xi)(xi)統(tong)(tong)維護和管(guan)理(li)的(de)工(gong)作量(liang)。
集中電源集中控制(zhi)系統(tong)的(de)(de)日常(chang)維護需要使系統(tong)定期進(jin)行自放電,應(ying)急放電時(shi)(shi)間小(xiao)于(yu)30 min更(geng)換(huan)(huan)產(chan)品(pin)或更(geng)換(huan)(huan)電池;系統(tong)的(de)(de)產(chan)品(pin)壽(shou)命應(ying)滿足有關國家(jia)標準(zhun)的(de)(de)要求,達到(dao)壽(shou)命期限的(de)(de)產(chan)品(pin)應(ying)及時(shi)(shi)更(geng)換(huan)(huan);當(dang)火災應(ying)急指示燈的(de)(de)表(biao)面亮度小(xiao)于(yu)15 cd/m2時(shi)(shi),應(ying)立(li)即更(geng)換(huan)(huan)。
集(ji)中電源集(ji)中控制系統還會出現一些常見故(gu)障,以下使(shi)其相對用的(de)其檢查方法:
1、主電源故障(zhang),檢查(cha)輸(shu)入電源是否完(wan)好,熔絲(si)有(you)無(wu)燒斷,接觸是否不(bu)良等(deng);
2、備用(yong)電(dian)源故障,檢(jian)查充電(dian)裝(zhuang)置(zhi)、電(dian)池有否損壞,連線有無斷線;
3、燈具故障,檢測燈具控(kong)制器、光源(yuan)、電池是否(fou)完好,如(ru)有損壞,應(ying)對此燈具故障部(bu)分及(ji)時更換;
4、回(hui)路通信故(gu)障,檢查該回(hui)路從主機至燈(deng)具的接線是否完好,燈(deng)具控制器有無損壞(huai);
5、其他故障,對于一時排除不了的故障,應立即通知有關專業維修單位,以便盡快修復,恢復正常工作。 //www.www69sihucomm.cn/