一,技術指標:
環境溫度:-20度----50度 交流(liu)電壓:220V 50HZ 充電電流(liu):30----300mA 充電時間:〈24小(xiao)時
光(guang)源功率:熒光(guang)燈(deng)(deng)(deng)(deng)(deng)6—58W 節能燈(deng)(deng)(deng)(deng)(deng)5—55W 電(dian)(dian)致發光(guang)屏2-4W
白熾燈(deng)(deng)(deng)(deng)(deng)15—100W。應急時間:〉90分鐘 電(dian)(dian)池終止電(dian)(dian)壓》80% 接線(xian)方式(shi):三線(xian)制 二線(xian)制
引出線(xian)顏(yan)色(se):常規照明火線(xian)—L—紅色(se),應急火線(xian)—L’—黃(huang)色(se),零線(xian)--黑色(se)(綠色(se))。燈(deng)(deng)(deng)(deng)(deng)具(ju)安裝方式(shi):吸頂,壁掛,懸(xuan)掛,側固定。燈(deng)(deng)(deng)(deng)(deng)具(ju)設置(zhi)主電(dian)(dian),充(chong)電(dian)(dian)故障三種(zhong)狀(zhuang)態(tai)指(zhi)示燈(deng)(deng)(deng)(deng)(deng)主電(dian)(dian)狀(zhuang)態(tai)用(yong)綠色(se),充(chong)電(dian)(dian)狀(zhuang)態(tai)用(yong)紅色(se),故障狀(zhuang)態(tai)用(yong)黃(huang)色(se)。僅用(yong)一個信號指(zhi)示燈(deng)(deng)(deng)(deng)(deng)的應急照明燈(deng)(deng)(deng)(deng)(deng)具(ju)可只用(yong)紅色(se)指(zhi)示燈(deng)(deng)(deng)(deng)(deng)。
二,安裝須知:
存(cun)放:應急燈具出廠前大都已放電處理。存(cun)放期(qi)超過三個月應充電一次,每次充電時(shi)間(jian)》24小時(shi)。
安裝:應急燈具(ju)應按規定位置安裝。**出口(kou)燈具(ju)通常(chang)設置在疏(shu)(shu)(shu)散(san)門口(kou)的上(shang)方,高度不低于2M;疏(shu)(shu)(shu)散(san)照(zhao)明燈具(ju)通常(chang)設置在疏(shu)(shu)(shu)散(san)走(zou)(zou)道及拐彎角1 M以下(xia)的墻(qiang)面上(shang);疏(shu)(shu)(shu)散(san)標志燈具(ju)安裝于樓梯轉角平(ping)臺處(chu)及疏(shu)(shu)(shu)散(san)走(zou)(zou)道上(shang)時,應有指示疏(shu)(shu)(shu)散(san)方向的箭頭標志。
配線:功能齊全的消防(fang)應急(ji)燈具應該是三線專線配置(zhi),和普(pu)通照(zhao)明分開(kai)(見圖一(yi))。**根線為燈具照(zhao)明火(huo)(huo)線L’中(zhong)(zhong)間(jian)可設置(zhi)開(kai)關(guan)(guan)控制照(zhao)明K。第二根線為應急(ji)燈具供電火(huo)(huo)線L
,此(ci)線從(cong)總電源開(kai)關(guan)(guan)下方(fang)專線敷設過(guo)來,中(zhong)(zhong)間(jian)不再設置(zhi)開(kai)關(guan)(guan),與**根線相位相同。第三根線為零(ling)線N。也有采用(yong)二線配制(見圖二),即僅有一(yi)根供電火(huo)(huo)線和一(yi)根零(ling)線。
注意:
1. 工廠(chang)在燈具配線時可能有(you)線色不(bu)一的現象,用戶安裝時要(yao)細心辨(bian)認一下,不(bu)清楚(chu)的時候可來(lai)電詢問。
2. 為避(bi)免(mian)在建筑承建期間不(bu)正常停電(dian)(dian)(dian)導致(zhi)應急燈因充(chong)電(dian)(dian)(dian)不(bu)足頻繁放電(dian)(dian)(dian)損壞燈管及充(chong)電(dian)(dian)(dian)電(dian)(dian)(dian)池,充(chong)電(dian)(dian)(dian)24小時后(hou)燈具才(cai)可正常工作。
3. 含有應急電(dian)(dian)源的燈具(ju)在現場安裝的時候必(bi)須(xu)斷電(dian)(dian)作業,在燈管沒有安裝完(wan)畢(bi)的時候不可通(tong)電(dian)(dian)。
附試燈(deng)程序如下:
安裝(zhuang)單個應(ying)急燈(deng)具試燈(deng):首(shou)先燈(deng)管安裝(zhuang)完畢,先送(song)應(ying)急燈(deng)充電(dian)電(dian)源L’然(ran)后再送(song)正(zheng)常照明電(dian)源L。次(ci)序不(bu)可以(yi)顛(dian)倒。
所有應急燈安(an)裝完畢后(hou)總試燈:首先所有燈管安(an)裝完畢,先送應急燈充(chong)電(dian)電(dian)源(yuan)L’然后(hou)再送正常照明電(dian)源(yuan)L,或者同時送電(dian)也可。但是次(ci)序不可以顛倒。
如發生包含應(ying)(ying)急電(dian)(dian)源的(de)燈(deng)具(ju)正(zheng)常照(zhao)(zhao)明(ming)通電(dian)(dian)不(bu)亮的(de)現象,應(ying)(ying)在檢查確保該(gai)應(ying)(ying)急燈(deng)具(ju)的(de)充電(dian)(dian)電(dian)(dian)源L′已經接通后(hou)(hou),將該(gai)套應(ying)(ying)急燈(deng)具(ju)的(de)正(zheng)常照(zhao)(zhao)明(ming)電(dian)(dian)源L斷(duan)開(kai)兩分鐘后(hou)(hou)再(zai)接上即可(ke)。(此方法目的(de)是使(shi)電(dian)(dian)子(zi)鎮流器異(yi)態(tai)保護狀態(tai)解除。)
保(bao)養:應急(ji)燈(deng)具(ju)投(tou)用后(hou)應有專(zhuan)人經常(chang)檢(jian)查(cha)維護(hu)(hu)發現異常(chang)情況應及(ji)時(shi)組織(zhi)檢(jian)修(xiu)或通知燈(deng)具(ju)廠家檢(jian)修(xiu)。應急(ji)燈(deng)機(ji)心(xin)(xin)是控制電(dian)(dian)池充放電(dian)(dian)及(ji)應急(ji)時(shi)點(dian)燃(ran)光(guang)源(yuan)的核心(xin)(xin)器(qi)件,其電(dian)(dian)路(lu)設計和元件質量的優劣直接影響到燈(deng)具(ju)的成(cheng)本以及(ji)電(dian)(dian)池和光(guang)源(yuan)的壽(shou)命。本公司應急(ji)燈(deng)具(ju)機(ji)心(xin)(xin)由**人員設計,零件嚴格篩選,恒溫錫爐焊接和測試室老化點(dian)燃(ran),質量優良,**可(ke)靠。在通電(dian)(dian)正(zheng)常(chang)使用后(hou)應每隔三個(ge)月放電(dian)(dian)一次,以對電(dian)(dian)池進行養護(hu)(hu),延長電(dian)(dian)池使用壽(shou)命。